Buzzer signalling
The buzzer on the motherboard provides the following signals:
Signalling |
cadence and tone |
activation |
deactivation |
---|---|---|---|
bop |
200ms, 500Hz |
Operation on user interface rejected. |
- |
beep |
50ms, 3kHz |
Operation confirmed on user interface. |
- |
alarm |
2kHz |
The smoke alarm threshold has been exceeded and detected. |
Button pressed Device reset Activation of an input with the mute buzzer function Resetting of the smoke level (if the automatic reset option is active) |
early-warning |
On 200ms / Off 200ms, 2kHz |
The smoke early-warning threshold has been exceeded and detected. |
|
fault |
On 1s / Off 1s, 2kHz |
A fault has been detected (activation of |
Button pressed Device reset Resetting of all faults. |
Note
The alarm signal has maximum priority.
The early-warning signal has priority over the fault signal.
The audible signalling of an alarm or fault by the buzzer are enabled via the “Audio signal on alert/fault” option, disabled at default.
The audible signals for confirmation or refusal of an operation (“beep” and “bop”) are enabled by the “Buttons tone” option, enabled by default.
The options are programmable via the local menu.