TCC-0001

IS Conventional audible and visual indicators

The alarm sounders listed below are certified for use in ATEX-classified environments for Group I (mining) and Group II (surface).

These sounders must be used in combination with a certified Zener or galvanic barrier.

  • Approved by ATEX, IECEx
  • Group I MI Ex ia I Ma
  • Group II IGD Ex ia IIC T6 Ga, Ex ia IIIC T85˚C Da
  • Zones 0, 1, 2, 20, 21 & 22
  • EN 60079-0:2012 + All:2013 (IEC 60079-0:2011) EN-60079-11:2012 + (IEC 60079-11:2011)
  • Dustproof & Weatherproof

TCC-0001-IS - Sonos Sounder - Red with deep base

TCC-0007-IS - Sonos Sounder Beacon Red deep base Amber lens

TCC-0008-IS - Sonos Sounder Beacon Red deep base Red lens

Current draw 33 mA
Sound output 105 dB @ 1 m
Wire entry 3x M20
Operating temperature -40°C ... +55°C
Protection grade IP66
N° of Tones 32 (internal DIP Switch)