Previdia Vox fire-detection control panel

Modular control panel with voice evacuation functions only

Basic control panel with only voice evacuation functions to which the FPM, FPAM, IFM and IFAM function modules can be added. The cabinet, model PRCAB+, is complete with plastic door and housing for the PTT microphone and emergency telephone.


Includes:

  • N°1 FPAMIAS Module - Control panel with display for Evac voice functions and public address
  • N°1 IFAMPSU Module - 1000W power-supply module with battery charger
  • N°1 IFAMEVAC Module - Audio matrix module for signals processing
  • N°1 IFAMAMP Module - 250W amplifier module
  • N°1 PTT microphone

Main features

  • Management of the EVAC functions (Voice Evacuation)
  • Integrated management of the Public Address functions (Sound diffusion and audio entertainment)
  • Input/Output modules for interfacing with control panels or third-party systems
  • Management of 8 local digital audio tracks and 8 digital audio tracks coming from the network
  • Management of up to 30 250W class D amplifiers
  • 1000W power supply included expandable up to 4000W (by adding PRCAB+ cabinet)
  • Impedance control of speaker lines by means of pilot tone
  • A/B lines management
  • Ring Speaker Line Management with optional isolators
  • Management of Backup amplifier
  • Management of two lines of standard and emergency microphone bases (max. 64 per line)
  • Internal audio memory for emergency and customizable messages
  • SD card management for additional audio
  • N°2 Analog Music audio inputs
  • N°2 analog audio AUX inputs with priority acquisition via contact or signal level
  • IDANET network on Ethernet point-to-point or optical fiber, max 48 control panels, shared audio
  • Possibility to connect up to 4 cabinets together (up to 3 additional PRCAB+)
  • Up to 1000 Audio zones
  • 2000 event buffer
  • Advanced management of audio Entertainment (see the IASS and IAC APP server section)
  • Customisable messages for each audio zone and for the different activation scenarios

Technical specifications of the Previdia Vox fire-detection control panel

POWER SUPPLY VOLTAGE

90 ~ 264VAC
47 ~ 63Hz

MAXIMUM CURRENT DRAW

8.5A @ 115VAC
5A @ 230VAC

OUTPUT VOLTAGE

26V DC NOMINAL
20 - 27,6 V

OUTPUT VOLTAGE ON SPEAKER LINES

100 Vrms

MAXIMUM CURRENT OUTPUT BY THE POWER-SUPPLY MODULE

38 A

CURRENT AVAILABLE FOR THE SYSTEM

35 A

MAXIMUM BATTERY-CHARGE CURRENT

3 A

BATTERY

2 x 12 V 17 Ah
or
2 x 12 V 38 Ah

OPERATING TEMPERATURE

-5°C .. 40°C

MAXIMUM POWER MANAGEABLE

1000W FOR EACH POWER-SUPPLY MODULE (MAX. 4000 W WITH 4 CABINETS E 4 POWER-SUPPLY MODULES)

IP PROTECTION GRADE

IP 30

DIMENSIONS

67,5 x 43 x 26 cm

CABINET COLOUR

GREY RAL7042
RED RAL3001

Previdia-VOX: Modular control panel with Voice evacuation and Public Address functions.

Previdia-VOXR: Modular control panel with Voice evacuation and Public Address functions. Red cabinet.