INE7-T

Detector in explosionproof enclosure

Explosion-proof enclosure detector, similar to the INE7 series detectors, equipped with an LCD touchscreen display. Thanks to this feature, calibration, verification, and maintenance operations can be performed without opening the enclosure.

This characteristic allows safe operation even in classified environments. 

The detectors from the INDUSTRIAL series are manufactured using the most modern reflow and SMT construction techniques. They use the latest generation of microprocessor technology to deliver fast response and ensure accuracy and reliability.

The sensitive element is connected to an interchangeable device component which allows installers to replace the sensor cap (the part susceptible to wear and tear) without needing to recalibrate the device.

The complete product line includes a wide array gas leak detectors, all available in explosionproof or dustproof enclosures to satisfy even the most exacting requirements.

During the installation phase or maintenance sessions, you can interface INDUSTRIAL series detectors with a PC (via an INA55-700 interface) or Android Smartphone (via an INA55-701 interface) in order to configure the parameters, change the intervention thresholds, check the gas-level readings and/or simulate alarm, pre-alarm and fault conditions.

  • Selectable delays from 0 to 240 seconds for each individual threshold.
  • Reading compensation system in accordance with ambient temperature.
  • Replacement of sensor cap directly on-site without need of titrated gas canisters.
  • Connection to PC (via INA55-700 interface) or Android SmartPhone (via INA55-700 interface) for threshold, filter and delay settings, real-time Value Readings and simulation of alarm, pre-alarm and fault conditions.

Orders for Detectors must specify not only the type of enclosure, but also the type of gas, the technology of the sensitive element and the type of output interface. Following is a schematic representation of the order codes.

TECHNICAL SPECIFICATIONS

Power supply voltage

11 – 30 Vdc

Standby current consumption

Semiconductor sensors

50 mA

Catalytic sensors

70 mA

Electrochemical sensors

30 mA

Alarm current consumption

Semiconductor sensors

80 mA

Catalytic sensors

100 mA

Electrochemical sensors

60 mA

Operating temperature

0 ... + 40 °C

Weight

 IP55 enclosure

370 g

ATEX enclosure

1000g

Dimensions

IP55 enclosure

141x100x60 mm

ATEX enclosure

165x90x80 mm

Maximum ambient air speed in the protected ambient

10 m/S

Following is a schematic representation of the order codes.


IN Suffix

IN

G = IP55 enclosure / E = ATEX enclosure

h

Industrial series (7)

7

Type of GAS (see table 1)

nn

Detector technology (see table 2)

t

Hyphen

-

Type of interface (see table 3)

ii


Table 1

Code nn

Gas detected

Pre-set Pre-alarm/Alarm thresholds

00

Methane (CH4)

15/30 % L.I.E.

01

Special Gas (see Order Code Table)

15/30 % L.I.E.

02

Petrol fumes

15/30 % L.I.E.

03

Carbon monoxide (CO)

100 / 200 PPM

04

Hydrogen (H2)

15/30 % L.I.E.

05

LPG (Liquid Petroleum Gas)

15/30 % L.I.E.

06

Propane

15/30 % L.I.E.

07

Ammonia (Pre-alarm at 100 PPM, Alarm at 200 PPM)

100 / 200 PPM

08

Ammonia (Pre-alarm at 1000 PPM, Alarm at 2000 PPM)

1000 / 2000 PPM

09

Acetylene

15/30 % L.I.E.

10

Oxygen (Excess)

24% / 27%

11

Oxygen (Lack)

18% / 15%

Table 2

Code t

Technology of sensitive element of detector

S

Semiconductor

C

Catalytic

H

Electrochemical cell

Table 3

Code ii

Type of interface

RL

3 Relays (Alarm, Pre-alarm and fault)

AS-C

Connection with conventional line (provides Pre-alarm, Alarm, Fault signalling. One detector only per line)

AS-M

Connection for addressable Input module - Inim model EM312SR

42

4-20 mA module

LE

Direct connection to Inim Loop

Related products

INE7

Industrial series Accessories

ING7