The SmartLine conventional fire-detection control panel series offers a:

2 zone non-expandable model (SmartLine020-2), /  4 zone model expandable to 20 zones (SmartLine020-4)   /  4 zone model expandable to 36 zones (SmartLine036-4).

The extreme compactness, trouble-free installation, uncomplicated programming procedures and simple end-user operation make this highly competitive control panel ideal for all small and medium applications, especially those applications where fast installation and programming are among the most important aspects of the system. The numerous functions (timers, equational logic, etc.), extensive flexibility (automatic output balancing, multifunction inputs, customizable outputs, gas function integration, etc.), and innovative connectivity capabilities (RS485 BUS for power supply stations, Internet connection, etc.), provide the tranquillity of knowing for sure that this powerful tool is capable of satisfying every need of every type of installation.

SmartLine020-2

SmartLine020-4

SmartLine020/4EXT

SmartLine036-4

SmartLine036/4Ext

The SmartLine conventional fire-detection control panel series offers a 2 zone non-expandable model (SmartLine020-2), a 4 zone model expandable to 20 zones (SmartLine020-4) and a 4 zone model expandable to 36 zones (SmartLine036-4).

The extreme compactness, trouble-free installation, uncomplicated programming procedures and simple end-user operation make this highly competitive control panel ideal for all small and medium applications, especially those applications where fast installation and programming are among the most important aspects of the system. The numerous functions (timers, equational logic, etc.), extensive flexibility (automatic output balancing, multifunction inputs, customizable outputs, gas function integration, etc.), and innovative connectivity capabilities (RS485 BUS for power supply stations, Internet connection, etc.), provide the tranquillity of knowing for sure that this powerful tool is capable of satisfying every need of every type of installation.

SmartLine control panels have supervised outputs (one on the motherboard and one on each added expansion) for the activation of audio-visual signalling devices, a customizable relay output, fault signaling outputs and two 24V outputs (one constant and one interruptible by installer-defined conditions). Additionally, each detection zone provides a terminal which can be configured as: open-collector output (activated by programmable conditions), supervised input, or Gas 4-20mA detector interface.

System information is provided through the graphic display and LEDs on the control panel frontplate. The RS485 BUS supports 4 remote repeater panels (SmartLetUSee/LCD-Lite). These repeater panels replicate all the fire alarm system data and allow users to access and control the system in accordance with their authorized access level. The BUS also supports two power-supply stations which can be connected in such a way as to allow supervision of their functionality and activation/deactivation of their output power during predefined conditions.

Programming the system from the control panel is straightforward and trouble-free thanks to the easy-to-follow instructions on the display. The system can also be programmed by means of the SmartLeague software application. This intuitive programming software greatly simplifies the programming procedure. The SmartLAN/485 board allows the control panel to connect to an Ethernet network for remote access via the Internet. Once the remote connection has been established, it is possible to modify the configuration parameters, upload/download programming data and/or manage the system by means of the supervisory software based on SmartLook graphic maps.

  • Conventional fire-detection control panel
  • Available with 2 zones, 4 zones expandable to 20, 4 zones expandable to 36
  • Certified EN54 / EN54-2
  • Certified EN12094-1 (Fire extinction)
  • Supports up to 32 devices per zone
  • Manages SmartLetLoose/ONE Fire Extinction board (Function EN12094-1 Approved)
  • 1 supervised alarm output (NAC)
  • 1 output for communicator/dialler activation
  • 1 dry-contact alarm output
  • 1 dry-contact fault output
  • 1 ancillary power supply output
  • 1 interruptible power supply output
  • 1 additional terminal per zone configurable as: open-collector output, supervised input, Gas detector input with 4-20mA interface
  • Battery shutdown relay for deep discharge conditions
  • Backlit graphic display for easy management of Installer/User interface
  • Navigation keys for easy access to graphic display functions
  • Fast keys (Silence, Reset, Evacuate, Investigate)
  • RS485 BUS for the connection of Repeater panels and Power supply stations (SmartLevel)
  • Buzzer (provides audible signals)
  • 8 Timers
  • 8 logical equations
  • Automatic balancing of individual detector lines
  • RS232 connector for system programming from a PC
  • Programming software
  • Easy system programming from the control panel
  • Access key for Level 2 functions (EN54 compliant)
  • Thermal probe for battery optimization
  • Battery efficiency test
  • Extensive application of SMD reflux technology for higher reliability
  • Metal enclosure
  • Mains power supply 230Vac
  • Switching power supply/battery charger 1.4A @ 27.6Vdc (for SmartLine020) or 4A @ 27.6Vdc (for SmartLine036-4)
  • Battery housing for two 7Ah - 12V batteries (for SmartLine020) or two 17Ah - 12V batteries (for SmartLine036-4)
  • Dimensions (HxWxD for SmartLine020): 325x325x80mm - (HxWxD for SmartLine036-4): 497x380x87mm
  • Weight (without batteries): SmartLine020= 3Kg; SmartLine036-4= 6Kg