Micra 10

Compact suction smoke detection system

The highly reliable Micra 10 is a compact, installation-friendly aspiration system capable of detecting smoke at the incipient stage of fire.

The “Classifire” algorithm implemented inside is capable of automatically optimizing the sensitivity of the detector to suit the environment where it is installed, thus eliminating the need for complex calibration operations.

Thanks to its output relays (dry contacts) this device is compatible with all fire detection system.

Stratos aspirating systems provide the very earliest warning of fire. They are capable of drawing air through sampling pipes to a three-dimensional laser chamber with a removable filter cartridge. The pipe length can be between 50m to 100m long, depending on the model and the level of sensitivity required.

The laser technology embedded in Stratos is capable of discriminating smoke from nuisance particles such as dust. This capability allows the system to reduce the false alarm rate yet still provide warning at the first trace of smoke, a feature which is particularly useful in applications that require extremely high sensitivity.

One of the most important features of the system is its capacity to self-calibrate, this feature determines the maximum sensitivity and reliability for the protected environment.

Stratos is equipped with a connector for RS485 line management for networked system purposes, or for data communications to remote sites. Useful relay outputs (Aux, Pre-alarm, fire 1, fire 2) allow Stratos to operate with both conventional and analogue fire-detection systems.

Stratos offers a comprehensive range of models with various features such as sampling pipes with several inlets, keypad and display and remote status indicator.

These aspirating systems have been designed to operate with traditional fire detection systems, therefore, they integrate with no problem in systems where multipoint and linear detectors are scarce. Stratos is capable of providing the very highest levels of sensitivity in environments such as computer and electrical rooms. In order to meet the demands of such applications, Stratos offers a series of devices which facilitate protection and provide warning at the slightest trace of smoke.

Seconds count in fire detection but so do maintenance costs and Stratos is a winner on both counts. As a result of the lowmaintenance requirements of Stratos systems, they find their niche in environments where maintenance and inspection are often difficult or costly, such as in false ceilings and or floating floors. The removable filter cartridge allows field serviceability even in the dirtiest of environments and is just one of the many features that make these systems advantageous and costefficient.

Different sensitivity and intervention thresholds can be obtained by simply adding or taking away air-flow inlets along the sample pipes. Such high-sensitivity coupled with advanced processing allow Stratos to be employed even in the most demanding applications. Stratos is supplied with PIPECAD programming facilities as standard.

Technical specifications

  • Power Supply voltage: 21.6V - 26.4V DC
  • Consumption: 250mA @ 24V DC
  • Dimensions: 145W x 220H x 90D
  • Weight: 1.7 kg
  • Operating temperature: -10 to + 60 ° C (EN54 Part 20)
  • Humidity: 0 - 90% non-condensing
  • Sensitivity: 0.03% to 25% obs/m
  • Detection technology: Laser
  • Detected particles: 0.0003μm to 10μm
  • Dust discrimination system: 3D3 Laser Dust Discrimination (LDD)
  • Maximum sampling pipe length: 50m
  • Sample pipe diameter: 3/4” (27mm)
  • Maximum number of sampling holes: 10
  • Detection levels: Alarm, Early warning
  • On-board relays: Early warning, Alarm, Fault
  • IP rating: IP50
  • Pipe inlet: 1
  • Exhaust pipe to expel the sampled air: 1