Digital NON resettables thermosensitive cables

Thermocables

Thermocable’s ProReact EN Digital Linear Heat Detection (LHD) cable uses fixed temperature detection technology to provide a straightforward method for sensing changes in temperature. The cable can offer alternative overheat protection in a vast range of applications and environments, from tunnels, cable trays, warehousing to sensing changes in temperature within escalators and other applications where many risks of fire are hidden from view.

ProReact EN Digital LHD cable is a non-resettable line-type heat detector. The two twisted cores and held apart by an advanced temperature sensitive polymer. At a temperature, set by the manufacturing processes of the cable, the temperature sensitive polymer surrounding the two cores softens, allowing the cores to come into contact. This is an irreversible process and once the cable has activated, the section which has triggered must be cut out and replaced (not the whole cable).

Control Unit

Model

Description

Approval

A1397

DSCU-EN Digital thermosensitive cable Control Unit, 2 zone

EN54-28

A1398

EOLU-EN  Digital thermosensitive cable End Of Line Box with Test facility,

2 Lines Termination

EN54-28

NON resettable thermocables

Model

Alarm temperature

Cable coating

Approval

F1182

68°C / 45°C

Low Smoke, Zero Halogen (LSZH)

EN54-28

F1192

68°C / 45°C

Stainless Steel

EN54-28

F1180

78°C / 45°C

Low Smoke, Zero Halogen (LSZH)

EN54-28

F1190

78°C / 45°C

Stainless Steel

EN54-28

F1181

88°C / 65°C

Low Smoke, Zero Halogen (LSZH)

EN54-28

F1191

88°C / 65°C

Stainless Steel

EN54-28